Account Holder? Login for Wholesale Pricing
 Call 1-800-661-9891   |   View Hours
Home  >  HVAC  >  Gas Valves  >  Residential Combustion Gas Valves  >  VR8200A2124

Resideo Honeywell Standing Pilot Gas Valve, 1/2", 24VAC, Single Stage, Set 3.5" WC, Standard Opening

  • Photo 1 of VR8200A2124 : Resideo Honeywell Standing Pilot Gas Valve, 1/2, 24VAC, Single Stage, Set 3.5 WC, Standard Opening

1 of 1
Click Main Image to Enlarge
Grids Shown are 1" x 1"

$27810
Special Order

 

SKU: VR8200A2124

Resideo Logo

 


Resideo Honeywell VR8200A2124 1/2", 24 Vac, Single Stage, Set 3.5" WC, Standing Pilot, Standard Opening, Gas Valve. This Combination gas control is for use with hot surface/direct spark systems in 120 Vac, gas-fired appliances, with capacities from 30 to 300 cfh.

Features:
Controls include manual valve, two automatic operators and pressure regulator.
Compact size.
Provides two automatic valves.
Solenoid operated first automatic valve opens on thermostat call for heat; closes when call for heat ends.
Diaphragm-operated second automatic valve opens under control of regulator; closes if gas or power supply is interrupted.
Meets codes requiring dual safety shut-off.
Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure.
LITE-RITE (OFF-PILOT-ON) lighting sequence
All adjustments, wiring connections and pilot outlet are accessible from top of control.
Includes One 3/4" straight flange; One 1/2" x 3/8" reducer bushing; Q340 Thermocouple; Natural to LP conversion kit
Mounting : 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
Stock shown on hand can change at anytime without notice or may already be spoken for. Please inquire by phone to confirm precise amounts available at that time.
Alberta
Edmonton (DC): 0
Edmonton (South): 0
Calgary: 0
British Columbia
Richmond: 0
Surrey: 0
Manitoba
Winnipeg: 0
Saskatchewan
Saskatoon: 0
Ontario
Hamilton: 0
London: 0
Mississauga: 0
Scarborough: 0
Windsor: 0
These are estimated number of days using averages of past orders for inventory arriving to each branch location and are not guaranteed. If you need to verify manufacturer stock please email customercare@amresupply.com or call us at 1-800-661-9891.
Amre Branch # of Days
Calgary: 21
Edmonton Downtown: 23
Edmonton South: 18
Hamilton: 20
London: 15
Mississauga: 18
Richmond: 22
Saskatoon: 19
Scarborough: 16
Surrey: 22
Windsor: 10
Winnipeg: 16


Product Specifications

  Body Pattern: Straight-through
  Capacity (kBtuh): At 1 in. wc p.d.-- 130,000 BTUh: 20,000 BTUh minimum: 200,000 BTUh maximum Natural Gas
  Dimensions (in.): 5 3/16 in high x 4 1/8 in. wide x 3 1/4 in. deep
  Dimensions (mm): 132 mm high x 104 mm wide x 83 mm deep
  Electrical Connections: 21 in. (533 mm) leadwires.
  Frequency: 60 Hz
  Ignition Type: Standing Pilot
  Inlet/Outlet Size (in.): 1/2 in. x 1/2 in
  Opening Characteristics: Standard Opening
  Operating Temperature Range (C): -18 C to +79 C
  Operating Temperature Range (F): 0 F to 175 F
  Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing
  Pressure Ratings (kPa): 3.5 kPa
  Pressure Ratings (psi): 1/2 psi
  Pressure Regulator: Standard
  Pressure Regulator Setpoint (in. wc): 3.5 in. wc
  Pressure Regulator Setpoint (kPa): 0.87 kPa
  Pressure Tapping: 1/8 in. NPT with plug
  Type of Fuel: Natural (LP with included conversion kit)
  Voltage: 24 Vac

Product Downloads
  Installation Instructions

Customer Reviews


  Add a Customer Review