ICM Controls ICM294 IPI Gas Ignition Control Module.
For use with intermittent pilot boilers, furnaces and other heating appliances. Microprocessor-based precision. Monitors timing, trial for ignition, rollout switch, flame sensing and lockout. Remote flame sensing. 100% lockout safety feature. Works with both Natural and LP gas systems
Replaces York 025-27762-700 and Johnson Controls G770RJA-1 series.
Specifications:
Control Voltage: Line 24V (18-30 VAC), 50/60Hz
Anticipator Setting: 0.2A plus valve load @ 24VAC
Prepurge: None
Trial for Ignition: 85 seconds
Flame Failure Response Time: 0.5 seconds
Retry: None
Weight/Dimensions:
Weight: 0.45
Height: 2
Width: 5.375
Length: 4